Determining the capacity and generation distributed optimal locations (DG) is one solution to improve the quality of the power distribution system. This research aims at finding the best solution for installing Distributed Generation (DG) on the distribution system using the Flower Pollination Algorithm (FPA) optimization method to reduce power losses. The FPA method is an optimization method by mimicking the phenomenon of pollination (pollination) of interest in nature. In the optimization experiment for location placement and DG capacity, the optimal placement on bus 3 is Gejayan Substation with a capacity of 4.9409 MW, and the power loss obtained in the system drops by 0.011MW. From the results of the optimization, it proved that the DG installation is able to reduce power losses in the Yogyakarta area distribution system. . Keywords: Distributed Generation, Determination of Location and Capacity, Flower Pollination Algorithm