Febriyanto, Nanang and Alfi, Ikrima (2018) STUDI PENEMPATAN SECTIONALIZER PADA JARINGAN DISTRIBUSI 20 KV DI PT. PLN UPJ KLATEN KOTA UNTUK MENINGKATKAN KEANDALAN. Tugas Akhir thesis, University of Technology Yogyakarta.
|
Text
Nanang Febriyanto_5140711022_Naskah Publikasi.pdf Download (1MB) | Preview |
Abstract
ABSTRAK Jaringan distribusi merupakan bagian dari sistem tenaga listrik yang paling dekat dengan pelanggan dan yang paling banyak mengalami gangguan, sehingga salah satu masalah utama dalam operasi sistem distribusi adalah mengatasi gangguan, sebab terjadinya banyak gangguan akan mempengaruhi indeks keandalan. Pada penelitian ini, dilakukan simulasi suatu model keandalan jaringan distribusi untuk mencari nilai indeks keandalan menggunakan software ETAP 12.6.0. Perhitungan ini berdasarkan nilai laju kegagalan (λ) dan lama perbaikan (r) dari masing-masing komponen yang digunakan dalam jaringan distribusi. Tiga penyulang yang dianalisis diambil dari Gardu Induk Klaten yang mencakup unit pelayanan jaringan Klaten Kota. Penyulang diambil berdasarkan hasil perhitungan nilai SAIDI dan SAIFI yang paling buruk. Penyulang yang diambil kemudian disimulasikan menggunakan software ETAP 12.6.0. Hasil simulasi nilai indeks keandalan sistem saat kondisi existing akan dibandingkan dengan setelah penempatan sectionalizer. Berdasarkan nilai indeks keandalan (SAIDI dan SAIFI) dari SPLN 68-2:1986, penyulang KLN01, KLN13, KLN06, KLN07, KLN08, KLN09, KLN10, KLN11, KLN12 adalah penyulang dengan keandalan yang baik, sementara untuk penyulang KLN05, KLN02, KLN03 adalah penyulang dengan keandalan yang kurang baik. Perbaikan keandalan pada penyulang KLN05 dengan menambahkan dua sectionalizer diperoleh penempatan dengan kombinasi lokasi penempatan SSO1 dan SSO3. Perbaikan keandalan pada penyulang KLN02 dengan penambahan dua sectionalizer diperoleh penempatan dengan kombinasi lokasi penempatan SSO1 dan SSO3. Perbaikan keandalan pada penyulang KLN03 dengan penambahan dua sectionalizer diperoleh penempatan dengan kombinasi lokasi penempatan SSO3 dan SSO4. Semakin banyak ditempatkan sectionalizer pada masing-masing penyulang, indeks keandalan semakin baik. Kata Kunci : Keandalan, Penempatan, Sectionalizer ABSTRAK Distribution network is part of electric power system that is closest to the customer and at most fault, therefor one of the main problems in the operation of the distribution system is to overcome the fault, because of many faults will influence the reliability index. In this research, simulation of distribution network reliability model to find the reliability index value using software ETAP 12.6.0. This calculation is based on failure rate value (λ) and repair duration (r) of each components used in a distribution network. Three feeders analyzed were taken from klaten substation which includes the service unit of Klaten Kota. Feeders is chosen based on the worst calculation of SAIDI and SAIFI values. Feeder which is taken after simulated using software ETAP 12.6.0. The simulated results of the system reliability index value when the existing cinditions will be comparated with after sectionalizer placement. Based on the reliablity index value (SAIDI and SAIFI) of SPLN 68-2:1986, KLN01, KLN13, KLN06, KLN07, KLN08, KLN09, KLN10, KLN11, KLN12 is a good feeder, while for KLN05, KLN02 and KLN03 is a feeder with poor reliability. Improved reliability of KLN05 feeder with the addition of two sectionalizers by placement with a combination of SSO1 and SSO3 placement locations. Improved reliability of KLN02 feeder with the addition of two sectionalizers by placement with a combination of SSO1 and SSO3 placement locations. Improved reliability of KLN03 feeder with the addition of two sectionalizers by placement with a combination of SSO3 and SSO4 placement locations. More and more placed sectionalizer on each feeder, reliability index is getting better. Keywords : Reliablity, Placement, Sectionalizer
Item Type: | Thesis (Skripsi, Tugas Akhir or Kerja Praktek) (Tugas Akhir) |
---|---|
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Fakultas Sains Dan Teknologi > S1 Teknik Elektro |
Depositing User: | Kaprodi Teknik Elektro |
Date Deposited: | 19 Nov 2018 03:23 |
Last Modified: | 19 Nov 2018 03:23 |
URI: | http://eprints.uty.ac.id/id/eprint/2375 |
Actions (login required)
View Item |